Revision history
2 revisions on file · 2024
-
Closed Rev 01 Issued Nov 01, 2024
Revision 01 - 1)Contractor advised that the existing channels across the ceiling, are carrying channels for plaster ceiling and are not suitable for gypsum board installation. New 7/8" furring channel… Read full revision note Show less
Revision 01 - 1)Contractor advised that the existing channels across the ceiling, are carrying channels for plaster ceiling and are not suitable for gypsum board installation. New 7/8" furring channels to be tied to bottom chord of joists.2)In lieu of application of intumescent coating on existing beams, Arcadis has proposed enclosing the beams in two layers of 5/8" type-x gypsum board, as per ULC NO. BXUV7 N501 (attached). This decision would help our client reduce the cost extensively.------------------------------------------------------------------------------------Installation of fire-rated gypsum board ceiling and ceiling mounted light fixtures in the Apparatus Room of the Station. - Fire Hall Station #331
-
Closed Rev 00 Issued Jan 10, 2024
Installation of fire-rated gypsum board ceiling and ceiling mounted light fixtures in the Apparatus Room of the Station. - Fire Hall Station #331
Every revision the municipality has published for this permit, read directly off the source record rather than the single collapsed status most permit trackers show.
Permit details
The municipal record for this permit.
- Issue date
- Nov 01, 2024
- Project value
- —
- Project type
- New Build
- Building type
- —
- Commercial category
- Institutional
- Description
- Revision 01 - 1)Contractor advised that the existing channels across the ceiling, are carrying channels for plaster ceiling and are not suitable for gypsum board installation. New 7/8" furring channels to be tied to bottom chord of joists.2)In lieu of application of intumescent coating on existing beams, Arcadis has proposed enclosing the beams in two layers of 5/8" type-x gypsum board, as per ULC NO. BXUV7 N501 (attached). This decision would help our client reduce the cost extensively.------------------------------------------------------------------------------------Installation of fire-rated gypsum board ceiling and ceiling mounted light fixtures in the Apparatus Room of the Station. - Fire Hall Station #331
- Permit status
- Completed City's exact wording: Closed
- Work type
- Building Additions/Alterations
- Completed
- 2025-02-04